Power network · Estimate: possible, not certain
Lower electricity transmission and distribution losses
Network loss: 8.5% of energy sent in 2024
If measures that cut power losses in other countries were applied, losses would fall each year by about
1,713 GWh Estimate: possible, not certain
enough for 92 thousand homes for a whole year
Range in the evidence: 1,713 to 5,825 GWh
If measures that cut power losses in other countries were applied, losses would fall each year by about
3,769 GWh Estimate: possible, not certain
enough for 203 thousand homes for a whole year
Range in the evidence: 1,713 to 5,825 GWh
If measures that cut power losses in other countries were applied, losses would fall each year by about
5,825 GWh Estimate: possible, not certain
enough for 313 thousand homes for a whole year
Range in the evidence: 1,713 to 5,825 GWh
11 thousand GWh arithmetic gap to the OECD average, on two different definitions (rough comparison)11 thousand11 thousand
Range in the evidence: 92 thousand to 313 thousandWhat the numbers show
Published figures show network loss fell from 10.83% in 2020 to 8.51% in 2024 [1]; the OECD average is 5.71% on a different definition [2].
2019: 9.4 → 2020: 10.8 → 2021: 10.3 → 2022: 10.1 → 2023: 9.5 → 2024: 8.5
What was tried elsewhere: comparison
Comprehensive loss-reduction programmes
Measuring actual losses, then fitting automatically read meters and regularising irregular connections.
Losses from 22% to 9% in Bogotá; from 15% to about 7% in El Salvador [4] — Bogotá (1997–2007), El Salvador (after 1998)
Strength of evidence (how far to trust it): Low
Thicker conductors on main lines
Replacing line conductors with thicker ones of lower resistance, so less is lost in transmission.
High-voltage line losses cut by 10% to 40% depending on area [3] — Modelling of British networks, 2018
Strength of evidence (how far to trust it): Low
Rebalancing loads between lines
Moving which switches stay open so electricity follows shorter paths with less loss.
Technical losses cut by about 17% [3] — Modelling of a British network, 2,286 feeders, 2018
Strength of evidence (how far to trust it): Low
Voltage control in the network
Setting network voltage at a level that reduces technical losses.
Technical losses cut by about 5% at most [3] — Modelling of British networks, 2018
Strength of evidence (how far to trust it): Low
How it was applied in published programmes
- Actual losses were measured by an energy audit; an audit in India raised the estimate from 18% to 38% [4].
- Large customers' connections and meters were inspected on site, and irregular connections were regularised [4].
- Meters read automatically were fitted for large customers, with sealed connections that made irregular hookups hard [4].
- Regularised customers were followed up periodically, then monthly or when metering data showed an unusual pattern [4].
Linked target
“… reduce carbon emissions by 278M tons annually by 2030”[source]
Published target: 278 million tonnes a year (2030)
This target is not measured directly by these figures.
Arithmetically about 0.9% of the amount in the published target (an approximate sum, not a measure of contribution to the target). Estimate: possible, not certain